Answer / k.prakashchandra
Insulation test,continuity test ,oil test and magnetic
balance test
Is This Answer Correct ? | 9 Yes | 1 No |
Answer / vinod g
Insulation Resistance,Winding resistance, Ratio test in
every tap positon from each tap rising and lowering,OLTC
continuity test , Tan delta of Oil and bushing, oil test (
BDV, DGA), magnetic balance test, polarity and
secondary/primary injection test for calculating the %
impidance
Is This Answer Correct ? | 4 Yes | 0 No |