In step down transformer (415/200V),mistakenly secondary
side is connected to 415V for some hours, what would be
result of this condition?
Answer Posted / ankaraju
The secondary side is rating of 200v,if you considering
loop the net current flowing throw winding increases hence
losses also increases and winding over heated,if it so on
for hours winding insulation may failed.And another one is
core is nearer to low winding,due to high voltage core
losses and core insulation between laminations also failed.
| Is This Answer Correct ? | 34 Yes | 5 No |
Post New Answer View All Answers
I am a possesor of c licence from 1993. I forgot to renew during the year 1998. During that time I was working at TNEB to till date. Is there any possibility to get renewed? or to apply for a new one?
how to compute kAIC? with formulas...
what should be the acceptrd value of winding resistance for 2.5MVA transformer
describe the fully control circuit diagram of ac drives
how to select the isolation tranformer for siemens 802dsl cnotroller
How we can determine short circuiting current any plant and for example a plant which power generation is 415 volts and plant load is 500 kw.
Define settling time.
what are the range of memory address in plc for L&T lx7 4A
Is it required to use Automatic transfer Switch in L&T panel board if we use AMF panel with DG set? How the single line diagram will be? Please forward the material to sreenu_207@yahoo.co.in
Why should be the frequency 50 hz 60hz only why not others like 45, 95 56 or anything , why should we maintain the frequency constant if so why it is only 50 hz 60hz?
why we used ZNO in Lightning arrester.
Did RMU have ct and pt ?
what is dry and wet frequency withstand voltage? why & where it is used??
how to calculate percentage impedence at 75 deg C at normal tap
hi frenz,its aswathy.i hve aplied for the hpcl test on feb,pls send the test patern & the placement papers as soon as possible. mail-id :kjaswathy@gmail.com