Make a list of materials and layout diagram for a 35hp motor, to be wired at 35meter away from the MDB in a chemical factory.
Answer Posted / waleed hourieh
P=35*746= 26.11 kw
I= 26.11 *1.74*1.25=56.7a
So the CB = 63A.
Materials list :
63A TP MCCB .25KA
63A/100mA ELCB .
60*60 MANHOLE COVER HEAVY-DUTY
35METER UPVC BLACK PIPE HEAVY-DUTY
4C*25MM2+1C*16MM2 Y/G.= 38 METER
63A TPN ISOLATOR
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
Differentiate between ideal and non ideal current sources?
Why i receive the GCU fault in my DG Sychronization panel . what all the factors considered for this fault .
Which device of PlC does share load between DG sets when DG are running in perallel?
what is a pulse transformer? how rise time of pulse changes when ever the voltage changes?
what is working process of star delta controlling circuit ?
what is an unbalance in acircuit? in a three phase 3wire circuit how an unbalance will come? in a three phase four wire system how an un balance is coming?
What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?
what is meant by moulded case circuit breaker ?
what is the use of sdf?
Is there any abbrevation for STUB in Stub bus protection
How many size of cable required for a 300m long and 30kw inductive lode
What is Auto Mains Failure Panel & Auto Synchronizing Panel
can i use 4 number of circuit breaker as single phase manual change over switch? if yes then how plz also send ckt diagram at nazimzamurad@gmail.com
What is the types of HT motor testing
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.