Make a list of materials and layout diagram for a 35hp motor, to be wired at 35meter away from the MDB in a chemical factory.
Answer Posted / a.yogeswaran
1 hp =750watts
35hpx750=26250
total load P=26.25
current I=26.25X1.74
=45.675(not in market)
=63A
cable size will be as 25cumm2 XLPE/SWA/PVC and 16cumm2 Y/G.CU.PVC.ECC(as required)
Breaker=63A 100mA ELCB Breaker
MDB 01 QUANTITY
Bus Bar Size=20mmx10mm
| Is This Answer Correct ? | 8 Yes | 2 No |
Post New Answer View All Answers
Why strting torqe high in inducation motor?
Usage of flywheel diode in relays
HOW CAN WE DECIDE THE SUPPLY VOLTAGE FOR MOTOR ACCORDING TO ITS RATING(IF ANYONE KNOWS GIVE IT WITH EXAMPLE AND ITS CALCULATIONS)
How can we findout the maximum efficiancy of Transformer? At which load?
How to dimensioning SDCCH, LAPD and CS7 signaling on GSM?
Could u pls tell me the NPCIL electrical engineering interview questions for Executive trainee, and also guide me how to face the interview.
If a transformer primary winding operates at 240v, the secondary at 120v and the load is 1500w & the transformer is rated at 92% efficient, what's the current flowing through the primary winding of the transformer? What is the formula for finding this?
what are the reasons of CT circuit faulty in busbar protection scheme?
Why is a synchronous motor always star connected??
when the time of backcharging the transformer three phases only enough or three phase with neutral is must.from these which one is the best one.
why ht cable end termination don't have a gland?
take 100kva DTR( delta/wye ), what ll happen if we connect 11kv to LT side instead of connecting to HT side? will the DTR behave as a step up transformer or something else????
Is it true online ups having bypass mode if it is true then why we called ups because it is interrupting power when goes in bypass mode
please send the IS strandard for electrical to sakthi_murugan86@yahoo.co.in
Define average demand?