I have one problem for masoneilan displacer type LT.I give some imformation in data shéet given for liquid level range 0 to 600 mm and sg .955 problem is 0% is ok 25%(23%) or 50%(48%)and 75%(73%) and 100% is ok this is up value and down value all ok so please halpe me
Answer Posted / rijesh
i hope that your calibration liquid you using is water[sg=1]. and your service sg=0.955.if so it is give you the output as per your observation
please make your calibration sg and service sg same value.
if you using service sg =0.95 and you using water for a measurement your maximuma span will be 95% and accordingly step change will effect.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is The specifications for oriface instalation
Speedtronic system .
Explain the mechanism behind the turbine meter.
can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?
why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V
on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon
1.what is the power consumption of three element drum level control in sugar industries? 2.how to reduce that?
If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?
Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram
Do you have reference list?
Explain bernoulli’s theorem.
how to calibrate corollaries (Mass flow meter)?
What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?
What is the use of single seated valve?
I need to know steps to Calibration Valve Guard......