I have one problem for masoneilan displacer type LT.I give some imformation in data shéet given for liquid level range 0 to 600 mm and sg .955 problem is 0% is ok 25%(23%) or 50%(48%)and 75%(73%) and 100% is ok this is up value and down value all ok so please halpe me

Answer Posted / rijesh

i hope that your calibration liquid you using is water[sg=1]. and your service sg=0.955.if so it is give you the output as per your observation
please make your calibration sg and service sg same value.
if you using service sg =0.95 and you using water for a measurement your maximuma span will be 95% and accordingly step change will effect.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?

1410


what is cold loop? difference between hot and cold loop?

1742


I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.

1895


how to calculate the total flow in square root

1746


What is instrumentation control?

652






OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION

10298


what is the PC interface and software for connection to ABB logic module “ LM011-CE18RAC “ ( for Programming ) ??

3438


Operational amplifiers

1524


why orfice is not used for main steam flow calculation

1605


What is the main difference between Cavitation and Flashing?

13431


what is diffrance between FF & SMART, explain with difination

2695


What is the PLC configuration in Cement industry?

3271


Give 2 application of quartz crystal used for process parameter measurement.

1584


Can any one tell me what type of question asked for instrumentation and control interview panel??? pls mail ramashankar.goel@gmail.com

491


Which Signal hart communicator work? If there any signal change when hart connect while transmitter in line ?

930