I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.
Answer Posted / hosam
you have 100kva pole type TX
POWER 100x0.8= 80 kw
total load aprox: p= 47 kw
tx capactiy rate 47/100 =% 47 load
the resistance of earthing to be less than 3 ohms.
cable cu 70 squ mm to load 47 kw lengh 100 mtr
%e1= 0.0124(47x100)/70= 0.85 tolal load
from tx to panels supply 32.5 kw lengh 50mtr cable 4cxm35 mm squ + 14.5 kw lengh 25mtr cable10 squ mm
%e2= 0.0124(32x50)/35= 0.56
%e3= 0.124(14x25)/10= 0.4
%e = %(0.85+0.56+0.4)= %1,81 < %3
total of the voltage drop is acceptable
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Is it possible to download the Siemens Selection Chart(TYPE 2 coordination) for 1) fuseless selection 2)Fuse selection
What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.
Would you recommend to replace all oil filled cables with xlpe cable for hv transmission with the current technolgy for xlpe cable?
Which type of air compressor is used now a days in the market. Keeping in mind of energy efficiency and maintenance points. Relevant documents may also be sent on mentioned email ids.
Hello sir, pls send me hpcl technical test papers .i am. Appearing for the exam.
What is dynamo?How it works and what is the function of dynamo in a DG.
What is contract demand in solar system?
Why is the frequency not changed during transformation of electrical energy in a transformer?
What is quadrantal symmetry?
when we have to use UPF wattmeter and LPF wattmeter? what is the difference between UPF and LPF wattmeter in terms of construction?
Why auxiliary transformers are not connected in parallel in primary stations?
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
Draw a 230kv two-bus bar system showing the following. 1.Two generators (150MW) each connected through one 15.75/230KV transformers 2. 1 outgoing lines 3. Two 230/130 KV transformers 4. BUS PT's 5. CT
A 500 V shunt motor runs at its normal speed of 250rpm when the armature current is 200A. The resistance of the armature is 0.12 Ω. Calculate the speed when a resistance is inserted in the field reducing the shunt field to 80% of normal value and the armature current is 100A.
How can maintain our H.T. motors used in cement plant. please send me procedure.