I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.
Answer Posted / hosam
you have 100kva pole type TX
POWER 100x0.8= 80 kw
total load aprox: p= 47 kw
tx capactiy rate 47/100 =% 47 load
the resistance of earthing to be less than 3 ohms.
cable cu 70 squ mm to load 47 kw lengh 100 mtr
%e1= 0.0124(47x100)/70= 0.85 tolal load
from tx to panels supply 32.5 kw lengh 50mtr cable 4cxm35 mm squ + 14.5 kw lengh 25mtr cable10 squ mm
%e2= 0.0124(32x50)/35= 0.56
%e3= 0.124(14x25)/10= 0.4
%e = %(0.85+0.56+0.4)= %1,81 < %3
total of the voltage drop is acceptable
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
in ring main system we use the isolater b/w transfer bus and main bus if we r not use isolatar than wat will be the effect in our sys.
What are the Full Forms of TVM, MTL, CVT ?
how the phase convertor changes the no. of phases
When will you multiply and devide with derating factors to the actual value while sizing the cable?
For high frequency application we use which transformer?
What will happen if a dc source is given to a tubelight. Will it work or wont it work....
Why does increasing the magnetic flux in the main field of a d.c motor cause the armature current to reduce??
differnce between single acting and double acting solenoid valves
How can calculate the rating of a servo stabilizer for given a specific load
pls tell us AC plant are how do work and parts name with picture
What is difference between slip rings and carbon burushes?
What are the types of excitation system?
How does a battary stores charge in it? please explain in simple manner and in detail.thanks
working principle of AC Servo Motor with its construction
What is the function of electron gun assembly used in crt?