WE ARE HAVING YOKOGAWA CENTUM CS 3000 DCS, 2 FCS AND 4 HIS "
When the operation Download to HIS message appears:
Equalize start. HIS0163
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. HIS0163
---- ERROR = 3 WARNING = 1 ----
Tell me, please, why and how to solve the problem."
Answer Posted / jaguirre
Dear Jigar Anadkat / Prashath,
This is the error.
Equalize start. HIS1145
WARNING: Could not connect to equalize destination. (7001) Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10061
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. HIS1145
---- ERROR = 2 WARNING = 1 ----
Regards,
John
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
What is the difference between modbus,fieldbus & profibus
How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?
Why are the uses 24vdc in industries
What is the minimum rating availalbe for weld neck orifice in market?
Please can anybody help for control valve sizing step by step procedure?
Coal mill Instruments Equipments for cement plant And process diagram ?
What is 1:1 redundancy ?
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?
what is maxdna ?. explain about the software details.
what is the working principal of pribe
give eg of how I/P is used in control loops
what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.
Can anyone convert a 5/2 way or 3/2 way valve into an ISO valve?
how many pulses are required by a ac induction servo motor of 4 poles with 50 Hz frequency to rotate by 1 degree?