?? how to calculate lighting system ????
Answer Posted / soumya
N=E*A/(F*U.F*L.L.F); N= number of light fittings required;
E = Lux required in working plane
A = Area of the room
F = Total Flux (Lumens) from all the Lamps in one Fitting
UF = Utilisation Factor = 0.46 (approx)
LLF = Light Loss Factor OR maintenance factor = 0.8 (approx)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
who many types of fire explane with exmple
how to calculate the breaking capacity of different breakers.
WHY RATING OF VCB NOT LESS THAN 630A
how generator load test is conducted?what are the steps?
how to calculate the formula of cable size if motor kw is given
What is meant by stator?
what is the chemical name and formula of refrigarent R-134a.
plz send me the syllabus or any sample paper for engineer trainee recruitment if any,on ravinder911@yahoo.com
Incoming line 11kv And transformer capacity is 2500kva. Consumption load is 1300A. Then fuse capacity is 11kv line.
RESPECCTED SIR/MADAM- I AM PRERING FOR SECTION ENGINEER (ELECTRICAL) RRB CHANDIGARH PLEASE SEND ME SOME PREVIOUS YEAR QUESTION PAPER OR MODEL PAPER.MY EXAM IS ON (30- NOVEMBER 2008).I AM VERY THANKFUL TO YOU. FROM- HARENDRA SINGH YADAV
why should small green grass ans small plant should not be there inside the transformer Yard in the factories
Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?
sent to a site and asked to explain how you would like a twenty seven flour building should be supplied with lighting and sockets plus a water boiler.
difrent between vcb acb sf6 and mccb breakers
What is the difference between amorphous core transformer and CRGO core transformer?.