Why is the length of cable layyed from RTD to temp. Transmitter should be minimum? Why does heating effect takes place in their?
Answer Posted / carl_ellis
Why is the length of cable layyed from RTD to temp. Transmitter should be minimum? Why does
heating effect takes place in their?
An RTD develops a very low voltage signal, on the order of tenths of a volt. Low level signals on
that magnitude can be overwhelmed by industrial electrical noise. And voltage signals, unlike a
current loop signal, diminishes (decreases) over distance.
There is also a limitation on the maximum wire resistance (which is proportional to wire length
and gauge) that an RTD input on a temperature transmitter or controller analog input can handle.
These reasons are why RTD temperature transmitters are so popular; the transmitter connects
close to the RTD minimizing noise and producing a current loop signal that is relatively immune to
noise and that does not decay over distance. The loop power is delivered over the same to two
wires as the output signal uses.
The self-heating effect is at the RTD element itself, it is not in the extension wire/cable
Unless it's a cryogenic (low temperature) application, the self heating effect is usually ignored.
Look at how little heat is developed:
A 1ma (0.001A) excitation current through 120 ohms (approx 52 Deg C) drops 0.120V (E = IR)
0.120V * 0.001A = 0.00012W or 120uW or 0.12mW
That's not a lot of heat to dissipate.
Carl Ellis
Measure First
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
3. Differentiate between ultrasonic flowmeter and radar type flow meter.
Hi, Is there any smart plant instrumentation design training institute in Bangalore?
What is the use of temprature compensation?
what is effect of specific gravity in differential level transmitter , explain formula related with this .
all types instrumentation questions want
What are different types of orifice plates? State their uses.
TECHNICAL/ARTITUDE
what is the difference between Cv and air consumption? why the customer needs Air consumption details?
What is zener diode? What is voltage regulator?
How to calibrate smoke Dectector
we want to control pump in let pressure and tank (for exp) our inlet line if water cam and pump will on and when our tank will full pump will off also if our inlet pressure low pump will off even tank not full.this pump i want to uses on our water supply line.
Specify for Cables - Flame Retardant and Fire Resistant?
sir,would you please send me the Hindustan petroleum corporation limited papers(HPCL).my e-mail ID is ujjwal_sharma1983@yahoo.com
how can be calibrate flow indication transmitter (rosemount) it shows excess milli amps nearly about 24 ma on full scale, but its scale was set on 20ma on full scale..???how can be simiulate..???
hi! i want to know about mpse exam.