Why we use 250 ohm resister in series
hart communicator?
Answer Posted / carl_ellis
HART communications requires a minimum of 230 ohms to
develop a sufficient voltage drop for the 1200 baud FSK HART
signal to be 'seen' by a HART communicator/modem.
The capacitance in a DC power supply acts as a low pass
filter which filters/strips off the FSK HART data.
Additional loop resistance is needed for HART communications
to take place.
If there is insufficient loop resistance, the HART
communicator/modem will fail to establish HART communications.
In normal field work, it is assumed that the analog input
to which the field instrument is wired will provide the
minimum resistance necessary. Most DCS analog inputs have
an input resistance of 250 ohms. But not all devices do.
And when bench testing/configuring HART instruments it is
not uncommon to connect a DC power supply, but not an analog
input. A HART communicator/modem will not work with just a
power supply powering a HART field instrument. The loop
requires a minimum of 230 ohms.
A 250 ohm resistor is commonly used for a bench
test/configuration because they're commonly available in the
instrument shop.
Carl Ellis
Measure First
| Is This Answer Correct ? | 15 Yes | 1 No |
Post New Answer View All Answers
What are different types of cable?
what deference between panel earth and systemearth
any questions on motor and energy conversions machines?
How to calibrate Toxic gas detector?
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?
How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.
What are advantages and disadvantage of the ac supply load cell?
Hello to all....I am an Instrumentation Graduate and i am passed out in this year only.. I am unable to find the job in my core instrumentation.. so any boby tell me how to and where to search the job....please...and also tell me i there are any courses offered in the instrumentation stream so i can do it... you can send your suggestions to my mail-id i.e Ganesh20084u@gmail.com ... please..
Define the difference between a stable versus an unstable controlled system and some of the tools you might use to be able to detect when this is happening and assumptions used for control system application design that could contribute to instability
Whatis the reset ofset and control system in instrumentation
i am preparing for BARC ,so plz mail me how to prepare for BARC. ALSO IF POSIBLE SOME RELATED QUESTIONS. MY MAIL ID IS khushi_4uall2003@yahoo.co.in
What is motion balance principle?
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com
whatis range of marcury filled tempereture gague