I have AC automatic voltage regulator 15KVA
What output currant?
Answer Posted / muzamil
if voltage regulator is single phage..in think its out put
I=kva*1000/230=65.21 amps...in full load,
if regulator 3 phage...I= kva*1000/415*1.732*pf*eff
=15*1000/415*1.732*.85*.85
=28 Amps.
| Is This Answer Correct ? | 7 Yes | 2 No |
Post New Answer View All Answers