11KW Delta motor is taking about 44Amps in star and goes
upto 70Amps in delta and trips OFF. The rated current is
26Amps. Application is for the blower. The motor takes ( no
load without coupling impller ) only 2.5A and 5Amps in star
& delta starter test.Need to know why its taking high
current.
Answer Posted / tj
Following is the check seq. :
1 Check for correct DOR/Phase Seq, ensure termination is
correct n tight.
2 Check the relay for malfunction & its type if it is
thermal then increase setting a bit more than ratd amps &
chk, n if its micro proc based then adjust the setting
acording to motor starting curve.
3 Ensure that suction damper is at min. before starting.
4 Ensure the motor is correct according to fan torque.
5 Check for any abnormal sound or play from fan side.
6 Also check the cable, it should not be underrated, causing
higher potential drop at startup.
Hope the above helps you........
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Why are lt windings placed near the core?
In a carnot engine with an efficiency of 40%, the heat rejected to the sink at 27 C is 60 kJ, then the heat supplied in kJ to the engine by the sources is
Discuss about gear cutting machines.
How much ph is maintained of water resistance starter for slipring induction motor ?
is that a problem if i connect a single phase load to a secondry delta connected transformer but i get a neutral from other transformer i the system?
STATE WORKING OF VACCUM CIRCUIT BRAKER?
why swityard is necessrry requirement in any bis power distributin systems?
if a.c supply is given to the motor,, what happen?
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
Why PT voltages are measured with respect to ground? What do u mean by voltage or current polarized.
electrical ques
witch pump used in wtp
What are the special cables required for explosion proof wiring?
what is meant by LCR meter? where its useful ?
What is the difference between rated and per unit in transformer?