if a damaged 500kva transformer with %impedance 2.6 is
replaced by two transformers of 250Kva with different %
impedance will they be able to catter the load. what will
be the ratio of load on the two transformers if the %
impedance is in the ratio 1:2
Answer Posted / k.prakashchandra
The above is correct.But transformers with same capacity and
voltage having % impedances in the ratio 1:2, is not
believable.The load sharing will be in 2:1 ratio if they are
connected in parallel.
Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
In cable sizing calculation (determining the max route length of cable) why we choose the shortest length between cable length of full load current Iflc & starting current Istart?
what is the maintaining Cf in UPS.
what is the maximum temperature rating of a thhn insulated conductor?
Draw a circuit diagram in which if button is open we can use socket and bulb as a series test circit and if button is close than simple we can use socket as any load purpose.
when generator short circuit condition, the current how dissipates. or at short circuit voltage not available then current how can flow?
details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?
How generating electric power export to grid from the generating station ?
Draw the wave shape of armature current in a generator subjected to a sudden three phase short- circuit at its terminals. Define various reactance of generator from this wave shape.
How we calculate the current carrying capacity of H.T. cabel?
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.
v/f drive basic princeple
How can we find the breaking capacity of a Load breaker switch (LBS) fed from 11 kv supply??ex:50KA, 26kA etc???detailed step vice answer pls.
how to modify DOL control panel into Delta Y connection?
how do we calculate length of starting time and repeated starting of a direct online starter?
Classify driling machines.