how you can select circuit breaker for 2000kva transformer?
Answer Posted / foolinla
The capacity of a transformer depends on its rated voltage
and current. The load current varies depend on the voltage
of the transformer.
If this 3 phase 2000KVA has a primary voltage @ 4160V, then
the primary current is 278A (2000000/1.73/4160V)
If the secondary of this 2000KVA is 480/277 then the
secondary full load current is 2408A (2000000/1.73/480).
If the secondary of this 2000KVA is 208/120 then the
secondary full load current is 5558A (2000000/1.73/208).
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines
In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?
Is MEN and RCD related to each other ?? IF yes then how??
When distance between two pulleys is not fixed, the tension of belt is adjusted by a) driver shaft b) driven shaft c) adjustment screw d) belt
If short circuit ratio is high is it bad or good for a machine then tell the reason...
Define open loop control system.
How we can recongnise the phase displacement of transformer connection between primary & scondary...plzzz explain it with example.........
WHAT IS DIFFERENCE BETWEEN MANUAL CONTROL AND MAGNETIC CONTROL AND STATE ITS ADVANTAGE /DISADVANTAGE
how we can calculate the efficiency of a diesel generator ?
we have 15 ampere variyac but we want 30 ampere variyac what we do
During FEED, you will have all the information with regards to cable. How will you calculate the MTO for MV and LV Cables? what are your considerations?
what is the difference b/w ground & virtual ground?
Classify drilling machines.
PLS SEND THE RRB CHENNAI MODEL QUESTION PAPER my email id is ganesan98655@rediffmail.com
Define coil span?