i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?
Answer Posted / g kiran kumar
1. Check the wiring at all terminal blocks at field, at
control panel and at PLC for any loose connection.
2. Check the Transmitter supply.
3. Measure the output from Transmitter.
4. Check cable continuity.
5. Finally check the configuration of TAG in the DCS (may
be someone deleated accidently).
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????
How to fix back the valve actuator stem
send me HPCL paper
Explain about the leakage class of the control valves
I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.
How we connect a instrument with ground, Give brief explanation with help of diagram?
I am manjunath having exp in maintenance of chemical plants,know i want to do a design course INTOOLS,after doing design course can we get jobs in design field.sinve i dont have design exp..
please tell no. & add. of consultancy who recruit me in power plant as instrumen engg. present i m working in power plant as ass.t instrument engg. thanku mahesh 09226562826
What are the different types of thermistors used in industries? How to the operation of typical thermistor?
What do you know about gail?
Can anyone send most commonly asked interview question in Oil & Gas industry
flow transmitter formula?
How digital input and digital output 's are working in dcs
Draw a great bridge circuit.
Give 2 application of quartz crystal used for process parameter measurement.