Can anyone explain how the vector diagram of a transformer
which doesn't have name plate be found whether it is
Dy11/Dy5/Yd11 and so on?

Answer Posted / k.prakashchandra

Whether Dy or Yd can be ascertained from the bushings.To
find particular vector group ,CRO can be used finding
relationship between the current vectors.e.g.In Dy 11 I2R
lags I1R by 30 degrees Number 11 denotes position of minute-
hand in a clock.It can also found out by taking various
voltage measuremnts and analysing

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT IS THE MEANING OF BALANCED / UNBALANCED IN STABILIZER TYPES.

1974


define the non synchoronism of synchoronous machine in general g or m??

1451


WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)

1347


What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?

1724


What is diversity factor in electric installations?

716






What is the drawback of class b amplifier? How is this minimized?

672


IF TVM OF TRANSFORMER SHOWS POWER FACTOR ON 33 KV SIDE AS 0.97 LAGGING AND ON 132 KV SIDE IS 0.75 LEADING.IS THIS CORRECT.WHERE IS PROBLEM.

1866


What are Contactors? How they works and what its highest rating?

1548


what is 3rd Harmonics? how it is generated in alternator

8472


. How to calculate the Short Circuit Impedance in Transformer? How to calculate the Short Circuit Impedance in Transformer?

1632


I am about to write exam in RRB bangalore for the post of section engineer.please provide me with previous exam questions

1675


. What is Electrical Life & Mechanical Life of Circuit Breaker? 2. What is Electrial Life & Mechanical Life of Magnetic Contactor? 3. What is RCD, RCCB & RCBO? 4. What is the Between defferance of RCD, RCCB & RCBO?

2836


Explain Circuit Breaker Trip Characteristics in detail.

1677


What aturn on methods of scr?

711


what is the problem when i want to close a circuit breaker by local position it closes well.but when i close it in remote position it trips

1087