how you can select circuit breaker for 2000kva transformer?
Answer Posted / solver
gaurang you are right
also mukund is right
Dear ashish & sareer,
always remember that the LT side breaker of transformer
is only selected based on rated capacity of LT winding.
i.e. 2782 A in this case.
& no overloading is considered beyond capacity of
transformer winding.
besides that transformer is loaded to 80% of its capacity.
This makes the load current even lesser than the rated.
Hope you are satisfied by this answer
Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
Give atleast 20 alternating current apparatus and devices.
What is Instantaneous Earth fault relay,how will work
why does the magnetic balance tests at transformer?
what are the effects when a salient pole alternator is run at high speed like 3000 r.p.m?
how much value of resistance should connect to 15 kw, 6 pole 3 phase slip ring induction motor having RV-240, RA-42.
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
in dc series motor if field wdg is shorted then
CT Ratio of a energy meter connection is Red Phase : 100/5A, yello Phase : 50/5A & Blue phase : 100/5 A what is the overall Multiplication factor
why actual valve timing diagram is different than ideal valve timing digram of a 4 stroke engine?
What is the function of Governor in Hydro Power Station? What is the Function of Lightning Arrestor Voltage Transformer (LAVT)?
why we use the 100% and 95% stator earth fault protection for the synchronus generator ?
WHAT IS SHORT CIRCUIT STRENGTH OF 100 AMPS MCCB?
How to select a contactor? How many types of contactors are available
the typical output of a solar cell is........
what is KA rating and how can we choose switchgears on applications