why is the rating of transformer done in kva and not in kw.
Answer Posted / kirti
kVA is the unit for apparent power. Apparent power consists
of active and reactive power. Active power is the share of
the apparent power which transmits energy from the source
(generator) to the user. Reactive power is the share of the
apparent power which represents a useless oscillation of
energy from the source to the user and back again.
It occurs when on account of some inertia in the system
there is a phase shift between voltage and current. This
means that the current does not change polarity synchronous
with the voltage. But the heat generated in a winding as
well as the eddy current losses generated in a transformer
core depend on the current only regardless of whether it
aligns with the voltage or not.
Therefore the heat is always proportional to the square of
the current amplitude irrespective of the phase angle (the
shift between voltage and current). So a transformer has to
be rated (and selected) by apparent power.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what is submersible pump?what is different between motor and sub motor?
Explain about 3 phase motor fault current calculation with examples?
Difference between ac parallel circuit and ac series circuit?
In CTs tan delta point should be earthed , what is the reason behind it?
Is it possible to connect a safety device in to parallel?
What is the diff. between single compression and double compression gland
What is thresh hold value of current?
what is servo motor and how to work it.
direction of tarbine& genrator
what is the differebt between ac and dc fuse?
the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?
what is different between relay and plc?
Why should be the frequency 50 hz 60hz only why not others like 45, 95 56 or anything , why should we maintain the frequency constant if so why it is only 50 hz 60hz?
I am a possesor of c licence from 1993. I forgot to renew during the year 1998. During that time I was working at TNEB to till date. Is there any possibility to get renewed? or to apply for a new one?
Hi Everyone ! My Name is Hakim ullah khan please i need formula of Cable Rating because i want to calculate by self without check any Table Chart... Thank you.....