how you can select circuit breaker for 2000kva transformer?

Answer Posted / gaurang

As per Equation

P=route 3 * V *I* cos phi
I=KVA/ rout 3 * V
So for 2000 KVA Transformer and considering Volatge 415 V.
I=2000/1.732 * 0.415
I=2782 A
Considering the breaker rated capacity selection above 2782
A as per Mfg. std.
Circuit breaker capacity will be of 3200 A.

Is This Answer Correct ?    26 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the lower limit of break-down voltage of converter transformer.

1459


How to calculate Grid rotor resistance(GRR) losses in slip ring induction motor?

3637


How many points does a Circuit can have?

1460


aternator every parts and its working

1188


i have applied for junior engineer 2 c&w for Guwahati RRB please send me last five year question paper

1599






how power trnafor from 1 point to another point in bus bar ya transmission line( voltage trnasfer from 1 point to another poin)

1497


what is the transmission loss for electrical supply? specifically a large shopping complex where the grid is half KM away, what will the % of transmission loss? is there any transmission loss for captive unit generation for above set? thanks

1538


why do you add the load short circuit impedance when considering short circuit amperage. It seems that you should only consider supply. If you need to consider loads and you don't know what loads are to be added , what would be a good sub-transient reactance rating for the loads?

1399


how invertor convert the dc into ac give brif detail

1542


What is meant by control system?

670


What do you mean by an instrument transformer?

656


The loads are connected with phase and ground then why current flow as the loads ?

1492


i want to put single phase load on scott connected transformer,eventhough how to balance the transformer.

1421


On Which Pressure PRV is operated.

1281


what are the things that can cause a three phase motor to crawl?

2881