how you can select circuit breaker for 2000kva transformer?

Answer Posted / gaurang

As per Equation

P=route 3 * V *I* cos phi
I=KVA/ rout 3 * V
So for 2000 KVA Transformer and considering Volatge 415 V.
I=2000/1.732 * 0.415
I=2782 A
Considering the breaker rated capacity selection above 2782
A as per Mfg. std.
Circuit breaker capacity will be of 3200 A.

Is This Answer Correct ?    27 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

comparision between ACB and VCB

2007


how to check avr of dg set of 125kva

2242


number of I/O devices in siemense plc

1751


I am experienced with house and industrial wiring but I don't have any licence how can I apply an licence and which type of licence i can get i didn't complete deee just only experience

1316


HOW MUCH CURRENT DOES SYNCHRONOUS MOTOR TAKES AT SYNCHRONOUS SPEED IN NO LOAD CONDITION ?

1534






what is meaning of sympathetic tripping with respect to relays and give the values for current carrying capacities for copper and aluminium cables from 16sq mm to 500sq mm

4490


i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh

2738


Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?

3541


How efficiency of thermal plant can be improved?

854


why ten delta testing is carried out on power transformer

1458


what is the condition for YnD11

2197


How to findout raw or ups power? its not indicated in socket,

1641


PLEASE ANYBODY HAVE ELECTRICAL CIRCUIT DIAGRAM FOR CHMER PULSE CD 60M SPARKING MACHINE.PLEASE MAIL ME SUPRIYAAYYAPPAN@YAHOO.CO.IN.

2444


how does high earth to neutral voltage affect electronic equipment?

1053


can we use ZNyn11 transformer instead of Dyn11 transformer in distribution for effectively eliminating harmonics from the industrial loads.

4612