why contactor not provided between output of VFD and motor?
Answer Posted / nandan d shanbhag
Due to electromechanical bouncing of the contactor
contacts , voltage spikes are generated which in turn will
result in failure of smiconductors in the drive. However
due to eletrical regulaton if contactor needs to be
provided for electrical isolation then there must be delay
of 1 sec before starting the inverter after contactor is on
and contactor should be made of atleast .5 second after the
inverter is made off.
| Is This Answer Correct ? | 5 Yes | 4 No |
Post New Answer View All Answers
how to compute kAIC? with formulas...
WHAT KIND OF LIGHTENING PROTECTION SCHEMS CAN BE ADOPTED FOR THE FLAT ROOF OF BIG DIMENSION.
Why are short circuit ratings always 16kA,25kA,36kA and 50kA.Who has fixed these?
What is the difference between PS & metering CT (5p20,0.5 etc.)? Why in PS class CT only Vk is given ? Is PS class CT is more accurate than metering CT?
What is Plank's Law?
What is Negative Potential Bias
How to Calculate The Neutral Earth flat design calculation for the Synchronised generator (Gen 1-650Kva, Gen 2-725Kva
How to design the NGR Resistance
Can we use both Electrical & mechanical interlock between tow breakers? if yes how, please explain
what is meant by LCR meter? where its useful ?
For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?
can any one provide me a connection wiring diagram for a DG set control panel along with BOM?
Give some differences between open loop and closed loop?
is it possible to have dc motors on single chip
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps