I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.
Answer Posted / premgin
See dear the basic soultion to cable size calculatiion in
sismple form can be done like this
Vd= ( mv* I * lenghth)*100/(400*1000)
I u can calualte from the Kw value for the particular pf
simple P/554
L required length
mV is the volatage drop/amp/km that can be obtained for the
particluar size of cable from supplier
eg. for 4cx16 its around 2.5 for most suppliers
100/400 is just amultiplication factor for converting it in
to 3 phase
Now do calulation and check if voltage drop limit is below
2.5 or 4 as per your standards
Simple.
But be cutious this is the simplest method and suitabel
method,many factors like grouping factor,derating
factor,spacing factor,type of laying,etc has to be taken
for apt analysis
Software like E Tap can also be utilised
| Is This Answer Correct ? | 59 Yes | 43 No |
Post New Answer View All Answers
What is a single phase autotransformer?
Which type of air compressor is used now a days in the market. Keeping in mind of energy efficiency and maintenance points. Relevant documents may also be sent on mentioned email ids.
What is the formula to calculate the no load current of a single & three phase induction motor
Y phase plates are used in transmission line??? what is there need???
how to calculate the tarriff for an industry whose kva demand is 10 mva
what is zinc diffusion?
What is dynamo?How it works and what is the function of dynamo in a DG.
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
if 6 earth pit value is 1.5 ohm then what should be the number of earth pit to make the value .8 ohm
how to calculate energy of 3-phase motor?
How to calculate wire length,size & current? ( related to control panel)
defult setting in p220 micom motor proction relay for 11kv,640kw,f.l.a.-40a,1440rpm ht motor?
How to work E.L.C.B and how to connect in circuit.
Write the force balance equation of ideal dashpot element.
Why we use 4-20 mA Analog signal for the PLC input? Why not 0-20 mA? Why not 5-25 mA?