why earthing is not required on transformer prymary winding
side ???
Answer Posted / dj
Transformer Primary side is Delta Connected, so there we
dont provide Earth fault Protection thats why it is not
solidly earthed, only earthing is provide at transformer
body. But on the secondry side which is usually star
connected, we have to provide solidly earthing to neutral
so that we can use earth fault protection system.
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
Why use the vcb at high transmission system ? Why can’t use acb?
What is the difference between rulling span and wind span of of an Over Head Transmission Line?
how to minimize earth resistance upto 2Ω, if the resistance is 6 Ω ?
What are merits & De-merits of State-Space Method? What is series programming, parallel programming, general programming & direct programming ? And, difference between these programmings Techniques ?
How to calculate per unit impedance of transformer?
What are the temperature elements?
What is meant by reset level of the relay?
can anyone explain the star-delta motor control wiring ,which wire go where and how they operate?
what is transformor oil gread
what is the minimum clearance between a 11KV 150KVAR capacitor cell and series reactor.can a series reactor can be mounted in the same structure of the capacitor cells structure
Is there any specialised book to refer about fault level calculation both in MV and LV side??
Safety of on line ups
any one can explain what is the size of pvc,armoured, various sizes of powr cable dia?
what kvrah y we need to take the readind of that
Pls Breifly explain about UPS (Inverter,Reserve,Rectifier,Float voltage,Boost voltage).