i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?
Answer Posted / s. kanniyappan
Check the Sensor properly. if it is ok, then
1)check continuity between the sensor cables
2)tight the cables properly
3)check the transmitter supply (24vdc)
if it is not ok, then check the DCS analog i/p cord.
| Is This Answer Correct ? | 14 Yes | 0 No |
Post New Answer View All Answers
How do bending tubing provide better measurement than using tubing fittings such as elbows?
What are the types of control valves available
control panel design guidelines
A flange is used for instrument connection for a system with a design temperature of 316C (600F) and a design pressure of 1000 kPa (145 psi). What is the class rating of the flange to be used for this application? Explain your answer
HOW TO CALCULATE ACCURACY OF AN INSTRUMENT. WHICH IS COMPITABLE FOR USE.
i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?
Whatis the reset ofset and control system in instrumentation
Identification of control valve parts.
How to interfacing microcontroller with a DC motor
is motorized valve closed when power shutoff?
In Safe Guarding test what means by "Failed to Danger" ?
I have completed B.E. Instrumentation & control in 2009. i have 3 year industrial job experience in chemical plant.now, I want to join M.E. in external. so, Plese say easiet way and good institute name.
pls give me presant awerness quistion and answer in my emailid.
what are the documents(Construction point of view for a process plant) submitted by contactor initially entering in to new site for client?
How to calibration a control valve?