When charging a 20 MVA , 33kV/6.6kV transformer through
regulated (0-6.6 kV or 0-33 kV) source on no load , what
will be the maximum current drawn by transformer from
source and what sould be the source capacity.

Answer Posted / dinesh lokhande

Actually above answer is not correct as it is the full load
current.No load current is approximately 4 to 5 % of rated
full load current. hence considering the terminals (i.e HV
side or LV side) the current drawn from source will be 4 to
5 % of respective side rated current.

Is This Answer Correct ?    8 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

pls,send the previous year written test questions.

1448


what is self capacitance of inductor

1837


How many double suspension hardware fittings are required on a double circuit transmission tower?

1569


a simple c++ program to calculate simple interst with its data members as private

1389


can i able to get bhel previous exam question paper?

1699






why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?

2364


explain types of electric welding and its applications

1202


How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.

2331


what is the profesional board for electrical engineer what is thepast and during construction for electrical engineering

1466


What happens if we connect a single phase energy meter in reverse polarity.

1719


Could the power factor on electrical system can affect the registration of the kwhr meter or the CT/PT? 

1457


What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.

1500


why impudance relay used for medium transmission power system? why not others?

922


A double circuit with dog conductor 66KV Transmission line from wind farm evacuation to feeding substation having capacity of 25MW for transmission. Can same transmission network be considered for further expansion of Power & how much in MW. If we need to expand next 10-15 MW more will there any augmentation is required in transmission network? Kindly reply asap.

1685


Explain what is electric traction? Explain few advantages of electric traction system?

613