When charging a 20 MVA , 33kV/6.6kV transformer through
regulated (0-6.6 kV or 0-33 kV) source on no load , what
will be the maximum current drawn by transformer from
source and what sould be the source capacity.
Answer Posted / dinesh lokhande
Actually above answer is not correct as it is the full load
current.No load current is approximately 4 to 5 % of rated
full load current. hence considering the terminals (i.e HV
side or LV side) the current drawn from source will be 4 to
5 % of respective side rated current.
| Is This Answer Correct ? | 8 Yes | 2 No |
Post New Answer View All Answers
1.how many earth pits are required for 1000 k.w plant include substion , transformer ? 2. how many earth pits are required for 500kva generator.what is formula to calcute?
which metal is use in shunt
What Normal(Tangent) towers and Tension(Cut-point) Towers?
WHAT IS THE MEANING OF BALANCED / UNBALANCED IN STABILIZER TYPES.
What is the cut-off rate?
What are the different types of transformers?
How to calculate flow of water delivered by pump when pressure & size of pipe line is given
What are the properties of a resistor?
How many types are using in 220kv/400 kv swith yard
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
Can any one provide the inspection procedure of MIMIC for VFD panel? Details: If someone wants to have a mimic in the VFD panel what are inputs considered for the mimic(like on,off,trip) whether we are able to add speed variation in the mimic(if so how can we get) and what are the parameters to be checked in the MIMIC during inspection?
transformer phasor diagram under load explain it?
What is value of earth resistance required for substation and equipment earthing and what are the reference guidelines
What is an ideal transformer?
where solid grounding and where grounding through ngr done and why?