how to calculate circuit breaker capacity

Answer Posted / usama badran ali

el salamo aleekom

to calculate circuit breaker breaker capacity...there are
four steps :
1-indicate all actual nominal voltages and MVA of your
system
2-indicate the location of circuit breaker.
3-calculate the actual impedance between the known supply
to the point of fault at which near to circuit breaker.
4-then calculate:
a- short circuit current =
voltage of supply/((3^0.5)actual impedance)
b-MVA short citcuit=
(3^0.5)*voltage of supply*short circuit current
c c-breaking capacity=
MVA short citcuit*assymetry factor.
or
short circuit current*assymetry factor
notes:
Assymetry factor:1.5~1.6 for midium voltage
1.25 for low voltage
MVAshort circuit= fault level
breaking capacity: it is the value of peak current where
the circuit breaker is breaking.

Is This Answer Correct ?    8 Yes 11 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is basic difference betmeen normal & flame proof motor??

1491


Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output

1259


What are operating procudures & Safety precautions to be observed while operating OLTC in manual mode ?

1462


hi Is there any possibilities to find out the rotation of a shaft or something else by using electromagnectic waves or by IR rays.If s then can v change the dir., of rotation of the same by remotely?& how? plz dn't any1 say "NO r CAN'T"

1617


Why synchronous motor is used in power factor improvement,dc series in lift

1192






Explain the operation carried out in thermal power stations?

620


What is lc oscillator?

725


what is maxemo work permit procedure

1691


pls tell what are doing the three phase motor star and delta connetion with circuit diagram and control wiring .

1466


in the directional overcurrent and earthfault protection,normally we are setting the angle 45 deg lead for phase fault overcurrent and -45 deg lead for earthfault fro forward direction.but both the fault are operating on the same angle region only.why?how the relay will response?

1419


in wind mill use 2100 kw asychronous generator ( induction generator ) rotor voltage : 3300,stator voltage : 690, rpm : 1511 type : MRL063E04 ' we check rotor resistance magger value found following. R-EARTH - 00 M.OHM,Y-EARTH-34 M.OHM,B-EARTH- 33M.OHM R-Y: 31 M.OHM, Y-B: 00 M.OHM,B-R :33 M.OHM HOW CAN I TAKE DECISION?pls ans. quickly

1884


I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?

2588


What is critical disruptive voltage?

849


What is mean by STUB protection?

1582


what is the isolation transformer. what is the isolator?

1612