why firewall is build up between two transformer
(220/11kv,50MVA)?what should be the firewall height?what is
the clearance between firewall and transformer?
Answer Posted / rakesh singh
Fire wall is built up between two transformer to protect
one transformer in case of firing on the other
transformer,the hight should be 1.5 times of the height of
the longer transformer and minimum clearance between fire
wall and transformer should be one meters.
| Is This Answer Correct ? | 27 Yes | 5 No |
Post New Answer View All Answers
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
What current flows in the transformer primary when its secondary is open?
What is the complete procedure of erection of electrical panel in industry
hii this is ranjith from hyd... i want to know what type of questions they ask in interview...and hw the interview will go..? what subjects thay ask specially for electrical engg students?
The magnitude of sum of two sinusoidal av voltage is equal to 230 volt.the magnitude of each individual voltage is also equal to 230 volt.what must be the phase difference between voltages?
Why the standard of ambient teperature mentioned as 40 degree celcius in machines.
what are the advantages disadvantages of connecting high voltage block( 1:1 transformers) transformers between the turbo generators and busbars.
why Lightening Arrester Probe sharp at Top of telecom tower.
Explain the working principle of Synchronous Generator and Assynchronous generator?
Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?
HOW TO CALCULATE THE VT SIZING?
Will an earth leakage trip be activated if the component or wiring is faulty on low voltage equipment.Example An electrical Cat Scarer placed in the garden and water gets into the wiring.
what is the difference between switch yard to residential area.and how much required it.
What is Tachometer used to measure?
how to calculate differential current when we testing differential relay..suppose we have 1000kw generator,630amp VCB,what value we should put /inject so that relay trip the VCB? PLLZ justify ur comment