why contactor not provided between output of VFD and motor?
Answer Posted / revansiddappa p.h.
Basically contactor is used to make and break the circuit
like any switch. For handling higher current and volatge we
use contactor; not only for motors.
Between VFD and motor; contactor is not required.
Because VFD will have features like enable and disable.
VFD will use IGBT's inside for switching application.
As IGBT's are semiconductor ; switching is fast compared
to electromachanical type contactor.And IGBT's handles
larger currnts.By enabling or desabling of VFD we can
Start/stop motor(with speed command). If contactor is used
there will be some time difference in swithcing ON/OFF of
IGBT and contactor which may lead to failure of IGBT and
motor winding and insulation. So it is meaning less to use
conatctor and also cost will be more.
Is This Answer Correct ? | 23 Yes | 4 No |
Post New Answer View All Answers
how we decide wire gauge for ac or dc coil and what is the basic diff. B/w these two coil?
Is a d.c.compound motor is use as a booster? how?
what is the difference b/w UHVDC and HVDC(LIGHT)?
how are reversing the direction of rotation of dc motor
What is effect of harmonic current (Draw by VFD) on power system/ electrical Equipments ?
What is EMC filter in VVVF Drive ?
harmonics filter
What effect does a very low impedance have on the Voltage regulation? On the short-circuit current?
If you don’t have coal, salt and copper, then how would you earth your connection temporarily at a camp site.?
Why do you have to use Protecion relay with the function MTB ( Mechanical Trip Button ) for electrical system.
why do we carry out winding resistance test?
What is kirchoff ’s current law (kcl)?
what is mean by D.O. in distribution line poles?
I am using submission of two ct in one and half scheme for 67/67N protection. Both CTs star point is grounded separately near ct box.Will two point ground give wrong tripping to 67/67N during fault or no matter.
Earth leakage relay basic knowledge principle