What is the max demand on your transformer and your company?
Answer Posted / mohd. karim
i want to give answer of this que. by an Example:
**if connected load of our system( factory,
Works,plant ...Etc) is 1250KW(1.25MW)...it means our maxi
demand at PF 0.83 is 1506KVA (1.506MVA)
one transformer used for this load with rating PF 0.8,
11kv/0.415, 1500kva
***it means MD in KW is 1200KW
MD in Kva is 1500KVA (1.5MVA)
it means this x-mer is not suitable for this load because
efficiency of x-mer is maxi. at half load. for above
example, this x-mer is suitable for 600KW-850KW at
PF=0.83)
Here
** is the MD of Company
***is the MD of X-mer
| Is This Answer Correct ? | 25 Yes | 5 No |
Post New Answer View All Answers
what is the constructional difference between a power transformer and potentian transformer?
What are the uses of lead compensator?
What is meant by sag?
electrical ques
What is meant by full pitched winding?
How does a battary stores charge in it? please explain in simple manner and in detail.thanks
How to calculate the efficiency of Turbo Generator(Alternator) in general....?
How u can give the overload setting to any motor protection relay for a HT motors with formula and Example?
STATE WORKING OF VACCUM CIRCUIT BRAKER?
What is the basic principal, by which DC voltage level is increased more than the supplied AC voltage during conversion. As upto AC level it is contorrled by firing anlge but after maximum level how is it possible.Please clear picture. OR we have to supply the higher level AC?
How generating electric power export to grid from the generating station ?
How many types of faults are there in 3 phase power system?
How will A Medium voltage circuit breaker(11 kV voltage level) operate under short circuit fault condition whether It is having short circuit release like Low voltage circuit breaker or relay should be given?
what is KSR type transmission tower? What is LSR type transmission tower?
How to decide the size of the capacitor for a single phase induction motor say 2 HP ??