What is the max demand on your transformer and your company?
Answer Posted / mohd. karim
i want to give answer of this que. by an Example:
**if connected load of our system( factory,
Works,plant ...Etc) is 1250KW(1.25MW)...it means our maxi
demand at PF 0.83 is 1506KVA (1.506MVA)
one transformer used for this load with rating PF 0.8,
11kv/0.415, 1500kva
***it means MD in KW is 1200KW
MD in Kva is 1500KVA (1.5MVA)
it means this x-mer is not suitable for this load because
efficiency of x-mer is maxi. at half load. for above
example, this x-mer is suitable for 600KW-850KW at
PF=0.83)
Here
** is the MD of Company
***is the MD of X-mer
| Is This Answer Correct ? | 26 Yes | 5 No |
Post New Answer View All Answers
11000volt DG set carnt kaise banvay
Why we use duplex coil and hook switch in telephone system?
What is the estimated total hydropower potential of india?
In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.
electrical
can we install HT panel & LT panel side by side or how much clearance is required ?
What are the advantages and disadvantages of short-pitched winding?
What is tan delta & PPM in transformer? and whats its IS value?
How to Calculate Current Rating of SDFU (Switch Disconnector Fuse unit) for Protectionof Capacitor Bank connected to Busbar of 800Amp,in LV side of 11/0.433KV, 250KVA Transformer?
What is ideal IR values for ground and neutral.
concept of busbar and load dispatching..?
Why did lightening arrestor solid copper rod head is sharp on mobile tower top?
please give me all the Alarm .Trip ,Safety Relays & Conditions of UPS Systems mail me on ashokbabunhce@gmail.com
Explain dc generator with its types?
why moisture formation found in XLPE Armoured cable outer sheath