What is the max demand on your transformer and your company?

Answer Posted / mohd. karim

i want to give answer of this que. by an Example:

**if connected load of our system( factory,
Works,plant ...Etc) is 1250KW(1.25MW)...it means our maxi
demand at PF 0.83 is 1506KVA (1.506MVA)

one transformer used for this load with rating PF 0.8,
11kv/0.415, 1500kva
***it means MD in KW is 1200KW
MD in Kva is 1500KVA (1.5MVA)

it means this x-mer is not suitable for this load because
efficiency of x-mer is maxi. at half load. for above
example, this x-mer is suitable for 600KW-850KW at
PF=0.83)
Here
** is the MD of Company
***is the MD of X-mer

Is This Answer Correct ?    25 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Name the component u would expect to find in a switchgear assembly?

1580


Explain the working of any one cutting machine

657


How to calculate LT XLPE CABLE for 11 kv / 433 v , 1000 kva oil type transformer system?

1338


How to do bus bar short circuit calculation for 230KV/11kv, 60 MVA Substation?

4258


what r PID controllers?why they r used?what is there purpose?plz Explain in detail

1614






Why control of DC motor is simpler?

1934


what is a synchronizing lamp ?

982


What are the internal and external faults?

611


Sir, I have applied for the of Jr.engineer(Electrical & Electronics) & ASST. LOCO PILOT at ALL RRB BOARDS. please send me all RRB Boards solved papers in the year of 2001 tO till date. i requested send me the papers to my id as soon as possible (jet_0991@yahoo.com). (This is very urgent) Thank You,

1398


for a 500 KVA connected load, I calculated 30% of capactor for power correction. Even after using 225 KVR capactor PF is not improving. What could be reason for low Phase correction factor?

1524


can we do the star delta connection of capacitor for 3- phase motor starter.

1538


sir please send me techinical questions for junior engineer posting in bangalore railway i am diploma holder

1544


What is power distribution criteria for converting single phase unbalanced residential load to 3 phase star connected balance system. Does total KW converted to 3 Phase. Means Divided by root 3.

1834


which IS or IEC is used for earthing,breakdown voltage of transformer oil, hv/pd testing and all type of electrical testing

2204


why the active power flow of some line is increased when the active power of out is cut ?

1638