how you can select circuit breaker for 2000kva transformer?
Answer Posted / sareer ahmad lone
Ans.First you have to find out the full load current of the
transformer that is IL=2915A then as per NEC you have to
give atleast 25% that is 2915x1.25=3643.75A.So the nearest
size of Circuit Breaker shall be 4000A.
Is This Answer Correct ? | 8 Yes | 6 No |
Post New Answer View All Answers
why is using sensor?what is differece between photoelectric and proxmitty?
What is transformation ratio what it describes?
If we use 250A MCCB as a incomer in Control panel for a fault level of 50kA for one second ,assuming temperature rise from 85 Deg. to 100 Deg , Then what will be the Aluminium Bus-bar size for 250A MCCB? Explain in detail.
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
What is critical disruptive voltage?
WHY THE COLOR OF OUTDOOR TRANSFORMER IS BLUE ONLY???
How can you sized or estimate the ligthning arrester current rating?
what are the reasons of CT circuit faulty in busbar protection scheme?
Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.
how we calculate electrical load on a building according to area?
How could a garment factory benefit from renewable energy
we have 15 ampere variyac but we want 30 ampere variyac what we do
If any cable burnt how can we identify it burnt by high current of high voltage?
what is mean by kneepoint voltage? when it will happen? ( my doubt is, if CT secondary is open means ct get saturation or blas? what are factors are required for calculations? plz give currect anws:
why servomotor motor? where i apply for best output?