We do have a problem in the company that is one PT connected to PlC which is mean 1 out of 1 in PLC system we do have the PAHH is 55 mbar and PALL 8 mbar with a timer of 15 sec for the PAHH the problem started when PAHH goes more than the set point which is 55 it reached up to 71 but due to timer doesn't trip . We force it and we checked everything nothing there . We replaced the transmitter problem still there the reading goes more than the 55 bar the range for transmitte is 0- 60 mbar . So we did loop check , aculaizing valve , wiring all are okay . What the possible causes for this ???
2 5132Post New National Petrochemical Company Interview Questions
Benifits of yii over other frameworks?
Explain the some guidelines for sizing a psv for a fire scenario on a vessel in a refinery service?
where are the passwords for ITS stores?
Can method names be capitalized?
What is the life cycle of a bean in spring?
Table method sequences? Validate write and write methods? Need of write method?
Which algorithm is used in arrays sort?
As Derby is such a small DB, why do you prefer going for a Derby DB in a real-time project Implementation?
What are @functions? : bo designer
What are the tools required for developing android apps?
What is a defect age?
How to convince a person to open a demat a/c?
How to Set a defaultrouter?
Create a structure to specify data on students given below: Roll number, Name, Department, Course, Year of joining Assume that there are not more than 450 students in the college. 1.write a function to print names of all students who joined in a particular year 2.write a function to print the data of a student whose roll number is given