three phase 180kva diesel generator can take how much load
in amp and what is formula to get this?
Answer Posted / gins
Now a days DG manufactures assuring that the DGs can be
loaded up to 120% of its rated capacity. But it is always
good to design DG for a maximum load of 80% of the rated
capacity to get the maximum efficient running. In your case
You can load a maximum load of 125.8 kW at pf 0.85. So you
have to give an incomer of MCCB with rating suitable for
125.8kW.
W=root3 x VI x pf
so I = W/root3 x V x pf
I think 250A, 16kA, 4Pole MCCB with 80% plug setting may be
suitable for you.
Accordingly select your incomer with suitable kA rating
with respect to your total load.
| Is This Answer Correct ? | 20 Yes | 5 No |
Post New Answer View All Answers
Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?
Is it possible to use a S1 duty class motor for crane application (S4)? If not, why?
when we decide to use soft starter drive or vfd drive in mcc to operate apump?
hi frenz,its aswathy.i hve aplied for the hpcl test on feb,pls send the test patern & the placement papers as soon as possible. mail-id :kjaswathy@gmail.com
What types of high speed CMOS circuits have you designed?
What is transmittance?
at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)
Does the direction of rotation of d.c. Shunt motor would get reversed if the armature current and field current both are reversed?
what is d check in dg 1500kva
Transformer how to maintaince a check b check c check d check
advantage of motor design on higher power factor . normally motors are designed for .8 power factor. what is advantage of designing at .88 power factor
What is the kiosk parts, about them and their functions ? If anybody have some PDFs files or details about this plz send it on tawhidfaisal@Yahoo.com
What is different between Circuit breaker and Isolater?
How to Make relay co ordination chart for a Electrical power distribution of a plant
Can i use the B-curve MCB instead of C-curve MCB