HOW TO CALCULATE THE CAPACITOR RANGE FOR LOAD FOR PF
IMPROVEMENT?
EXPLE:FOR 65 HP LOAD HOW TO CALCULATE CAPACITOR RANGE?
Answer Posted / deepakindi1
Boss what if u dont have the table?
let Cos(@1) be the present PF
@1=cos'(@1) (cos inverse)
let Cos(@2) be the desired PF
@2=cos'(@2) (cos inverse)
KVAR required= KW[ tan(@1)-tan(@2)]
for 65 Hp load
KW= 65HP*0.746 = 48.49KW
Considering Preent P.F=0.50
desired pf =0.99
ie cos(@1)=0.5
@1=cos'(0.5)=60
@2=cos'(.99)=8.1
kvar=48.49*[tan(60)-tan(8.1)]
=48.49*[1.732-.142]
=77.08
kvar=77.08
| Is This Answer Correct ? | 54 Yes | 6 No |
Post New Answer View All Answers
why we use single core 630mm2 cable for transformer secondary side
What are the material used for resistor?
Hi, My plant daily consumption is calculated as 3.8MWH but my supplier has sanctioned an power of 2.6MW per day. how can i equal or distinguish this two factors
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
what is the minimum requirement gigaohms for the insulation test using 5kv in 300mm xlpe cable
difine electrical ballast in HPSVL
How many kw will suply from one db
hi frds, i m electrical engineer.can i get cdr for electrical engineer if u have then send me on my mail id its jayesh_ee88@yahoo.com.please help me frds
700KW 6.6KV slip ring induction motor to use VFD to control the speed
Which device of PlC does share load between DG sets when DG are running in perallel?
How to decide cable tray size?
15hp motor wound by 0.9mm & 0.95mm magnet wire. at no load test it draw 4.2A current. Another motor with same condition draw 9.2A current. How can that occur? pls help
How do the synchronizing lamps indicate the correctness of phase sequence between existing and incoming alternators?
what are the stresses in circuit breakers ?
solar inverters was not connected to the nuteral link .this nutwral possible to any other systems