Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to take Transformer oil Break down voltage test?

Answer Posted / dinesh kumar

TRANSFORMER OIL BDV is carried out as per IS-336 for nomal
and IS-12463 for High viscosity oil.
1.Take one sample from top of Transformer and one from the
bottom of transformer.
2.The BDV of oil should withstood min 50 KV
3.The gap between the test sample is 2.5mm maintained
4.Each sample(top/bottom) should be checked seperately
5.Procedure
a.Voltage should be gradually increased from 0.
b. At one point Flash will take place and that point is
termed as Bread down Voltage

Is This Answer Correct ?    119 Yes 10 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?

3307


What is trip and closing coil in cb? Why need of them

1530


How to calculate the heat load for a electrical room

3098


What is the function of probe in cro?

1221


what is mean by D.O. in distribution line poles?

1677


What is a dominant pole?

1171


What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.

2427


SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS

6851


What is precision of a measurement?

1127


What are the different towers used in 132kv transmission line? what are the differences between the P,R,S towers used in 132KV and detailed explanation

1922


given data are load current & power factor cable core size? plz any one update the calculation formula

1906


What is diversity factor in electric installations?

1187


How many devices can be connected in one zone of FACP

2327


I need model question papers for RRB section engineer Chennai... Please send to my E-mail Id:- maitheerainbow@gmail.com

1961


What is the function of electron gun assembly used in crt?

1192