Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

three phase 180kva diesel generator can take how much load
in amp and what is formula to get this?

Answer Posted / mohan

Formula:1.73 X V X I/1000

180X1000/1.73X415 =I

Full load current 250A.

But we should have take only 80%

Is This Answer Correct ?    131 Yes 20 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is effect on in zone and out zone fault if CT chosen for phase side is Vk/2<5mA and Neutral side is Vk/2<15mA on REF protection of Transformer

2438


THERMAL CAPACITANCE IS MEASURED IN..................................................

2199


How to select the proper VSD to operate high inertial load

1785


how we findout a ignater is faulty or not?

2159


what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor

2092


Define pole pitch?

1168


I WANT BHEL PREVIOUS QUESTION

2422


Dear sir, How to calculate 3.5 core pvc aluminium armoured cable meter wise carrying amps rating.Please give the solution with a good example.

1962


Is it possible to measure correct value of earth resistance & cable insulation ristance with out disconncting earth lead & both sides of cable ends? If not, any other method to measure ER & CIR with out disconneting from the system.

2161


How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).

2215


why we use two slope(differential & restraining) in differential relay.but in busbar protection differential we are using only one slope?please explain

2328


Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028

2028


what is formula for calculate thermal overload in new numiricalrelay( not in bimetal relay)?

2362


hi, could someone help me to find a control design for syncronising panel .

1777


What are the specifications for getting approval of Substation?

1989