WHAT ARE THE FACTORS REQUIRED FOR SELECTION OF TRANSFORMER
RATING?
Answer Posted / kannan.sj
first u should know
1,The connected load of transformer or load factor
2,Highest connected load / motor in the transformer and its
starting type
3, diversity factor
because
KVA demand at 0.8 p.f =connected load x LF x DF
-------------
efficiency X p.f
starting current of highest KW load takes 6 times of full
load current. so we to check it whether the transformer has
the capability to feed the load or not during starting. its
the important thing while considering trafo selection..
| Is This Answer Correct ? | 57 Yes | 6 No |
Post New Answer View All Answers
what about electrical pannel.? What is meant by plc pannel.?
how to carried out tan delta test in 11 KV alternator ?
why do we not use equivalent voltage source in negative sequence equivalent ckt.
DG SET BLOCK DIGRAM
How do you calculate the actual power consumption of an inductive load appliance. Say, a deep freezer of 200watts
For small size, high frequency coils, the most common core material is- a. )Air b. )Ferrite c.) Powdered ion d.) Steel
how can i change the rotation of the AC single phase induction motor and show me by diagram
what is circuit recombiner and how it is different from circuit breaker
Can we use both Electrical & mechanical interlock between tow breakers? if yes how, please explain
What is vaccum currcuit breaker.define with cause and where be use it device?
Please send 110 kv sb station full single line drawing(sld)
we have 2.2kw,Y,3000rpm motor but 6leads found in TB what happen if we connect in delta?
Explain about Leakage Test.
how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.
What is the reason that the humming sound is coming from the induction furnace panel?