How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva
oil type transformer system?
plz provide step by step calculation
Answer Posted / engr. md n h shabuj
S=(Ish *√t)/K
=(10.49*√1)/0.143
=73.35
=75Rm cable
Ish =P/ (√3*V* % of Z)
= (1500*10^3 )/( √3*11*10^3*7.5%)
=1049A
Ish =1049*10=10490A=10.49KA
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is the difference between type1 and type2 relay protection co-ordination for motor feeders
Operation carried out in thermal power stations?
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
mccb service sittings be done?
how to decide no of electrodes for 1600A LT Main incomer panel
define digital electronic
previous year paper of ntpc bhel for degree in electrical enng
Draw a 230kv two-bus bar system showing the following. 1.Two generators (150MW) each connected through one 15.75/230KV transformers 2. 1 outgoing lines 3. Two 230/130 KV transformers 4. BUS PT's 5. CT
What is the Resposiblity of Electrical Utility Engineer
what is meant by vector group of a transformer? How can it be derived?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
How to calculate no of EARTH PIT? Describe the formula as per IS standard?
Generation of voltage for each phase are same of a turbogenerator.Although the short circuit current flow when two phase of turbogenerator are shorted(where current can't flow without potential difference),why?
hi, could someone help me to find a control design for syncronising panel .
What the main causes of transient interruptions on Over-Head Distribution Lines?