phase association of 3PH L&T static CT meter is wrong.
means 1PH & 1 CT connected properly and other 2 voltage and
CT's inter changed. what would be the impact in the reading?
Answer Posted / shankar
Lets us understand this problem by taking load as constant and the incoming supply initially it was RYB in sequence.
let Vr=10<0 Ir=5<-10
Vb=10<-120 Ib=10<-20
Vc=10<-240 Ic=15<-10
Now the total power is P=VrIrcos(-10)+VyIycos(-140)+VbIbcos(-250).
=41.5 watts.
Now lets us consider Y and B phases were wrongly connected to each other
Vr=10<0 Ir=5<-10
Vy=10<-240 Iy=10<-20
Vb=10<-120 Ib=15<-10
Now the total power is P=VrIrcos(-10)+VyIycos(-240)+VbIbcos(-130).
=3.781 watts
so the energy meter will records less units
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
What is George phenomena to start the synchronus machine?
A cylindrical wire is compressed in length by 10%. The percentage decrease in the resistance will be?????
In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?
Classify driling machines.
internally connection of photvoltic module
What is bridge rectifier and explain with details
In ups static switch if i gives the supply at output end it will open the circuit in stactic switch or not if it will open then how it operates.
Why the efficiency of a three-phase induction is the motor is less than that of a three-phase transformer?
What is hipot test procedure?
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm
Define norton equivalent circuit?
advantages & disadvantages of Lagging and leading power factor .
how to find the voltage's of a transmission line plzz help with pictures i am not able to understand
how we test a 3 phase motor on single phase supply....? HOW WE RUN A 3 PHASE MOTOR ON SNIGLE PHASE. supply for testing..? how we verify of a 3 phase motors 6 wire & name thame a1/a2/a3..b1/b2/b3 and c1/c2/c3 for connecting star delta starter ........i have only 1 phase supply ? help forum..........