1 ton AC takes how much current( starting & stable)
Answer Posted / tony
All the answers are actually wrong. MCBs can handle quite a larger current (2-15 times, depending on type) for short period of time so you don't consider inrush current.
Type B: 3-5 times
Type C: 5-10 times
Type D: 10-20 times
The breaker in the distribution box usually is dependent wire gauges. You can adjust the mcb with socket according to load.
Use type C for ac. Only use 1.5 times of the running current. I use 13A for 1.5 ton ac.
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
how many joints are allowed in underground HT cable of 1 KM
why induction motors are rated at 0.8 power factor.
Explain what is use of lockout relay in ht voltage?
How to work definite,over pluxing,revers power,OSR relay
how much value of resistance should connect to 15 kw, 6 pole 3 phase slip ring induction motor having RV-240, RA-42.
I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.
which protection function should measure RMS value of current&DFT value of current?
What is dc current source? Differentiate between ideal and non ideal current sources?
hi I have done 3 yrs diploma in electrical engg after 10+2. I have 16 years of work experience into design proposals sales and engg application development in LV/MV swithcgear and sub station automation field. I want to apply for immigration to new zealand but I am not sure whether I qualify or not since I dont have a degree. Can anyone advice? Thanks Riz
HOW TO SET THE EARTH FAULT SETTINGS IN ACB????????????
What is a Phase shift meter? Where can I get one?
What are IR values and what it should be for coil and for insulator
can any one tell me about the Extra low voltage systems?From where we give supply to these type of systems??
What is control system?
Hi Friend I am used multimeter to measure the voltage between R Phase(SS1) to R Phase(SS2). In SS1 is connected with UPS loads. But I am getting voltage between these 2 R Phases. Please give some idea friend