In 6600/√3/110/√3v voltage transformer,how much output
voltage in open delta transformer,after removing 1-phase of
primary side on transformer?
Answer Posted / 7anoter4
The open-delta connection it is actually 2 single phase transformer in series.
The voltage between two high voltage terminals it is 6600 V and each secondary
phase presents 110/√3 V[ some time even 100 or 110V].
If all three H.V.phases are connected the voltage between secondary terminals[in direct series] is 110/√3<0o +110/√3<120o=-110/√3 V<240o or oppositely connected 110/√3<0o -110/√3<120o=110 V<30o .
If the removed phase it is an extreme one then only one transformer stays connected [two voltages at ends] and the voltage is 110/√3 V.
If the removed phase it is the middle then both transformers stays connected with only one 6600 V and the voltage is 2*110/√3/2<0o=110/√3 V[or 110 V] for direct connection or 0 if they are oppositely connected.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the formula to find out two phase active & reactive power
can someone explain that how the speed of the protection system affects the fault level calculation?
Sir, plz tell me how droop setting is done in parellel operation od DG set ? please give practical example ?
what reason of line current and phase current in star connection and line current and phase current not equal in delta connection?
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
how indusrial diesel generator work
If one tertiary phase i.e. R,Y or B is earthed of a loaded type tertiary delta connected (Without load)of a power auto transformer, what is its advantage/disadvantage?
what r substations?what r there work?why voltages r incresed and then reduced during distribution of power
he compression ratio for a petrol engine generally lies between
what is interfacing in computer studies?
how can we design robots
calculate external resistance values to add to the rotor of a slip ring induction motor. STATOR- 415 V, 3 phase delta, 1100 A, 50 Hz, 1490 rpm, pf 0,86 ROTOR - 660 V, 590 A, 50 Hz. STATOR current at each steps STEP1-600A,STEP2- 800A,STEP3-1000A,STEP4-1100A.
what is the question paper model for section engineer in RRB
Whether it is possible to measure energy at the input of rectifier transformer (12 pulse with very high odd harmonics)
DG Earth Value?