Why we Specify Transformer rating 433 V Instead of 415V
?
Answer Posted / andy d
It is to do with the transformer % impedance, As mentioned open circuit LV side of a transformer would measure 433V, Fully loaded the transformer volt drop is equal to the % impedance. A typical 1MVA DY11 transformer would be around 5% impedance at full load, i.e. the secondary voltage reduces voltage to 411V. This is a lower value then 415V however it is not advisable to run transformers at 100% if you want a long life.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
if we run a 3 phase machine on two phase what will happend??? given answer with solid reason please
In vapour absorption refrigeration machine fluids used are
Explain and give me an example of a time when you had to explain some new procedures to your co-workers for quality service delivery, how did you go about it?
What is CCT (Correlated Color Temperature) ?
(1)Can earth and be conected together (2) what is the diferent between earth & neutral
What are the advantages & disadvantages of a group electrive drive?
What is superposition theorem?
I am an American living in Vietnam and I have recently gotten a refrigerator from Japan and it is rated for 100 vac, but the power here is 220 so I bought a voltage stabilizer it has a 1 kva output rating. Can you please tell me what the amperage is? I'm confused and without a working fridge.
for a 500 KVA connected load, I calculated 30% of capactor for power correction. Even after using 225 KVR capactor PF is not improving. What could be reason for low Phase correction factor?
how to find Harmonics and types as per the equipemnts
What are the factor to be consider for CT selection in 132kV substation?
Who are the manufacturer for Nitrogen based Fire Protectio/explosion prevention for Oil Filled Transformers? India and international both?
what is stper motor
any earth foult trip the relay but in welding time not trip by earth foult
How 3 phase invertor works?