If the load of transformer is getting more than its
rating,,,than how to overcome this problem? Suppose thee
rating of transformer is 315kva and the load is going
beyond than the rating say around load: 352kva...
Than how can we solve this problem without deducting the
load.
Answer Posted / kumar
Imagine 352 kva load operating at the pf of 0.8. If you're increasing the power factor to 0.95 by using static or synchronous capacitor the the kva will reduce to 274 kva and the transformer now meet the demand comfortably
Apart from this the other method is to connect another transformer in parallel with the existing one
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is meant by celling voltage & current in excitor ?
What is the real function of reverse power relay in generator panel while syncronising?
Draw the vector diagramme for Asynchronous Induction Generator at noload,half load and fullload.
WHY TERTIARY OF POWER TRANSFORMERS IS LOADED WITH EQUIPMENTS LIKE CT,PT,ISOLATOR AND CB
what is diff. between earthing grid,earthing mess, earting grid?
If we have 11 kv RYB Phase single core cable near about. Then wht effect and losses
pls tell what are doing the three phase motor star and delta connetion with circuit diagram and control wiring .
How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V
work of choke in florocent tube circuit ?
Difference between transition and diffusion capacitance
detailed procedure how we calculate cost for pcc m10 and rcc m20 including centering and labour excluding steel/ iron
how to calculation increase power factor for single phase
Explain The Application Of Storage Batteries?
how the works electronic energy meter?
How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?