We in my plant one of the transformer showing neutral to
earth voltage is 22V how to solve it
Answer Posted / aditya199307@gmail.com
Such types of problem occur due to increased in value of earth pit.
So 1st you checked the all earth pit values individually by opening all the grounded connections.
As per standard the values of earthing in HT yard should be less than 5volt.
If the value is greater than 5 volt then apply the procedure to reduce the value, which is different as per type of earthing (Normal or Chemical).
If the values should be comes as per rated value your problem is short outed.
If you talking theoretical part then voltage between N & E is zero.
But practically 2 volt is permissible but i.e. also not good for the system
It will affected on electronics system.
Such types of problem occur in the hilly areas or in rocky soil.
( If the value will not coming as per standard then add n....number of earth pits in series otherwise use counterpoise method.)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
There are a trformer and an induction machine. Those two have the same supply. For which device the load current will be maximum? And why?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
what is residuel magnetism. and how order lead acid batteries for 24 volt. emergency lighting system.
what is the necessity of under ground cables ??
what is meant by motor startup supervision & motor load jam protection ?
how to calculate energy of 3-phase motor?
surge tank, hrc fuse, earthing transformer, firm power objective type
How will you define capacitance?
Instrument connected to a single phase supply
Can an inverter be used as a converter? How?
If any cable burnt how can we identify it burnt by high current of high voltage?
What do you mean by phasors?
can we use engine degreaser for electrical motors?
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to reconfirm its base capacity.
how pt is using