We in my plant one of the transformer showing neutral to
earth voltage is 22V how to solve it
Answer Posted / aditya199307@gmail.com
Such types of problem occur due to increased in value of earth pit.
So 1st you checked the all earth pit values individually by opening all the grounded connections.
As per standard the values of earthing in HT yard should be less than 5volt.
If the value is greater than 5 volt then apply the procedure to reduce the value, which is different as per type of earthing (Normal or Chemical).
If the values should be comes as per rated value your problem is short outed.
If you talking theoretical part then voltage between N & E is zero.
But practically 2 volt is permissible but i.e. also not good for the system
It will affected on electronics system.
Such types of problem occur in the hilly areas or in rocky soil.
( If the value will not coming as per standard then add n....number of earth pits in series otherwise use counterpoise method.)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
I WANT YHE TECHNICAL AND ELECTRICAL SPECIFICATIONS OF 2x4MW 11KV 2x10MW 11KV 2x25MW 11KV 2x100MW 11KV HYDEL POWER PLANT i.e PROTECTION SYSTEM,MONITORING,CONTROL SYSTEM,GENERATION,SYNCHRONISATION,METERING PLEASE SEND THE DETAILS TO MY MAIL ID SPRAVEEN_222@YAHOO.CO.IN
What is transient response?
If a transformer primary winding operates at 240v, the secondary at 120v and the load is 1500w & the transformer is rated at 92% efficient, what's the current flowing through the primary winding of the transformer? What is the formula for finding this?
How much ph is maintained of water electrolyte which is used in LRS for 1200 kw slipring induction motor ?
by using pump duty, how we will can calculate the motor duty(KW)? is there any standard or formula.
what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?
why should small green grass ans small plant should not be there inside the transformer Yard in the factories
why the check zone and main zone are used for Busbar Protn. scheem?
What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works?
Explain Creepage Distance of Insulator
can someone explain that how the speed of the protection system affects the fault level calculation?
How seriving & testing of the HT & LT breakers are done. What are the standard Ir values on which we can come to know the test is passed or failed?
How does a television work?
IN dc capacitive reactance is??
explain the mode of metal iranafer in Co,welding