Answer Posted / srinivasan rengarajan
it is used for sensitive earth fault protection , especially when the feeder CT ratio is very large & max EF current to be sensed is very low as much as 5A or 10A.. This kind of C.T namely ring type CT encompases all the phase cables ,the secondary side of it is
connected to a sensitive EF relay, whose contact will in turn be connected to trip coil of CIRCUIT BREAKER.Under no fault
conditions the vector sum of all the three phase currents
is zero; so no output to c.t secondary but when there is an
earth fault ,the sum would not remain zero (it would be 3 I0- namely 3 times Zero phase sequence currents) and the trip
coil would act and circuit breaker would trip.
The fact that it would not detect phase to
phase fault,is not a disadvantage, because the very purpose of CBCT is that it is specifically designed for sensitive earth faut protection or earth leakage protection.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Why do we use copper cable for HT Supply and why not Aluminium?
What is shutdown of electrical sub station?
could you measure current in parallel?
What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?
either water sensor or flow meter,how we observe the water level, f any other equipment are in market ?
I have done my m.tech in electrical engg discipline. Can any one please suggest me how should I prepare for getting into phd in iit or nit.How should I prepare for getting into lecturership
mostly the questions were from machines... d.c. machines, transformer, synchronous and induction all theory paper........ few from power system... but the level of paper was easy.....
explain me the relation between torque, frequency,speed,voltage and current in the 3 phase induction motor?
block diagram of 2 ups system connected in parallel mode?
what is the function of statics switch in ups and tell me parts
Inductor and capacitor........power in one phase and ...... in it another phase.
what is the cause of voltage dipp or swell in the transmission lines?
can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?
What is class ab operation?
What will happen if we on 200kvr capacitor bank(11kv in bus)If there is low load on transformer (1.5 mva 33/11 kv)