How can calculate ups battery back up time?
Answer Posted / basanta das
Ups Standard Bacup Time = (Battery Volt X Each Battery Ah X No. Of Batteries) / load in VA
For example: Volt 12 x AH 26 x Total batteries 16 = 4992
Now divide the above with required load (1 KVA) =1000VA
So result is 4992/1000 = 4.992 hours
Means your UPS will run for 4.992 hours in standard calculation method, but in actual there will be a UPS energy waste or dissipation, let your UPS efficiency is 80% then you will get actual time
4.992 x 0.80 = 3.9936 hours i.e approx. 4 hours of backup time for 1KVA load if you have 12volt, 26AH battery of 16 nos.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is difference between speed mode and torque mode in motor?? explain in simple words please.
what is the saturation point of crgo lamination.
What will be the effect of circulating current in HT xlpe cable when both the armour ends are grounded. Will the termination fils after some time in case of 33 kv supply.
PLEASE TELL ME ABOUT QUESTION PAPER OF UPCL ENTERENCE EXAM.
Draw the line diagram of diffretial relay connected to transformer?
what is the affect of earth's magnetic field on the frequency used in aircraft???
how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.
If a current -8+6sin6t is flowing three ammeter, one is a centre zero PMMC meter, one is true rms meter and one is moving iron meter. What are the reading of these three meter respectively?
What is the most accurate way of testing ELCB?ELCB is better than RCD?
What is a difference between indoor transformer and outdoor transformer of same rating
Hi everyone. Some Generators uses 3-Pole breakers with extra contactors for Neutral. Some uses 4-Pole. Why so? What is the idea behind this? Thanks in advance for the solution. Kr.
i am trying to PSUs/govermeant jobs since last 2 years but still i m not success, plz help me.
how to calculate the surge level of surge suppressors related to the SF6 cicuit breakers?
which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?
for hipot test on 33kV busbar, we will test on 70 kV or 56kV, what is the acceptable leackage current?