how to calculate the multiplying factor for energy meter
with CT ratio given
Answer Posted / avinash pawar
MF = Main PT ratio × Main CT ratio / Meter PT ratio
Main PT ratio = 22kv / 110v
Main CT ratio = 400 / 5
Meter PT ratio = 11kv / 110v
So, MF = { 22000/110×400×5 } /11000/110
MF = 160
Is This Answer Correct ? | 0 Yes | 2 No |
Post New Answer View All Answers
What are the different power system losses and how can it be eliminated?
If VFD is On but no starting commond on it. so how many outpout voltages of VFD
I have made a 3 phase thyristor full bridge rectifier. But at the moment it is working only for the half bridge operation. Both the half bridges are on operation separately but when i put it into full bridge operation the oscilloscope output is zero. I rechecked that the pulses are correct for each thyristor. what could be the possible reason for this?
What is real time power factor control panel(RTPFC)?
What are the necessary solutions needed to be carried out on a malfunctioned earthing mechanism of a VACUUM CIRCUIT BREAKER.(TAMCO)
What is dc current source?
How many sprinklers should be in one pipe line?
how to calculate magnetic force genrated by a coil ?
CAN WE CALCULATE THE NEGATIVE SEQUENCE AND ZERO SEQUENCE REACTANCE OF A GENERATOR USING ONLY ITS RATED VOLTAGE, KW, PF AND SYNCHRONOUS REACTANCE??? IF YES, THEN HOW??
What is the effect of pd controller on system performance?
what happened when we supply a dc current in dc motor?? can it worked properly?
how to conduct dc resistance test for rotor of an alternator and how to measure the rotor dc resistance value theoritically?
Is it possible to make a 5P10/ CT Ratio 50/1A Burden 5VA
Why L.T.Cable voltage rating is 1.1kV,where as system voltage is 0.415kV?
what is the principle of the single phase energy meter? and,what is the advantages and disadvantages of single phase energy meter?