Why capacitor bank does not require in DG Set?
Answer Posted / saeed
The field excitation current requirement for a loaded generator depends very much
on the power factor of the load current and in the usual case of lagging power factor
the field current increases as the power factor reduces. On the other hand, with
leading power factor loads the effect is the opposite and as the power factor reduces,the field current requirement for a given output will go down. If the leading power factor of the load circuit is reduced sufficiently, a condition may be reached in which the field current requirement becomes zero and this is known as self-excitation. At this critical point the AVR sensing the generator output voltage would lose control, and any further reduction of the leading power factor would cause overexcitation and the voltage would rise without any corrective action from the AVR. Such a condition is obviously most undesirable and could cause damage to the connected load.
Because self-excitation depends on armature reaction effects from the stator
winding, modern a.c. generators which have high synchronous reactance will reach
this point of voltage instability at a lower level of reactive load than older type
machines which tended to have lower synchronous reactance values. Circuits which have any risk of self-excitation should be carefully examined before arranging to feed them from a generating set supply and in doubtful cases it may be necessary to adjust the values of the power factor correction capacitors.
To prevent voltage instability and voltage transients it is recommended that
power factor correction capacapacitor banks should be disabled when only the standby generation is running.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Dear sir, In our plant have Station Transformer having capacity,i want to know, why LV side 40 - 40MVA is given? & how we can get 6.3 KV supply from tertiary(i.e. Open delta connection), Vector Group YNyn0 - yn0 +d MVA Rating 80MVA / 40 - 40MVA + 26.7MVA Voltage rating 420 (Tap range +6,to -10)81.25% /11.5KV - 11.5KV +6.3KV
From past few months I am getting lagging pf even though sufficient capacitors used in circuit. Where is the problem pls answer
What is synchro?
I want d.g.set our company
how many electricity poles are there and what are the names and their sizes.
what is formula for zero phase sequence of nuetal earthing transformer of 6.6 kv
which type of motor is used in automatic swing gate
How to calculate multiplication factor in kva example 500kva ans pls ?
Would you recommend to replace all oil filled cables with xlpe cable for hv transmission with the current technolgy for xlpe cable?
should %impedance be high or low in a power transformer? if so why?
Differentiate between real and apparent power?
what is alluminium arm in ab conductors
What is diversity factor in electric installations?
What does quality factor depend on in resonance?
What is polar plot?