1.What is wind span ,wight span and normal span, and what is the difference for 132kv transmission .
Answer Posted / hanupowergrid
*The wind span is that on which the wind is assumed to act transversely on the conductors and is taken as half the sum of the two spans, adjacent to the support.In order to take full advantage of towers located on elevated ground, it is usual to allow a wind span of 10 to 15 percent in excess of
the normal span. This additional strength can be used in taking a samll angle of deviation on an intermediate tower, where the actual wind span is less than the design wind span. The angle of deviation to be taken in such cases is approximately given by:
θ =( wl /π T )x x180
Where w = total ind load per unit run of span length of all conductor
carried by the tower,
l = difference between the wind span used for design and the actual
wind span, and
T = the total maximum working tension of all conductors carried by the
tower.
*The weight span is the horizontal distance between the lowest point of the conductors, on the two spans adjacent to the tower . The lowest point is defined as the point at which the tangent to the sag curve, or to the sag curve produced, is horizontal. The weight span is used in the design of cross-arms.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
could anybody able 2 send me jindal steels previous papers fr electrical steam....pls send 2 my id if possible....sirisha.shaik@gmail.com
how we can set the IDMT relay.
what material is used in capaciter
What is an ac motor?
how to test YNyn0 vector group in transformer?
hai iam arunkumar. i have applied for an section enginner in rrb. i want lat 5 years solved question papers. if u have please sedn it to arun30682@gmail.com
what is the necessary of using inductance property in transmission lines even through resistance is used to opposes the high current flows in that?????
Haw to check conductivity of budbar
is that a problem if i connect a single phase load to a secondry delta connected transformer but i get a neutral from other transformer i the system?
List the advantages of star-delta starter with induction motor?
What is the mmf,rgt and ngt please brief completely
What are the conditions for sustained oscillator or what is backhouse criterion?
What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?
If there are two transformer having rating of 2.5mva, 6.6kv/440v(satr-star),and the load is 600kw then what is better to maintain less losses in transformer having both transformer in parellel or only single transformer connected to load? Please give calculated answer
wheather the size of windings in motor and generator are the same