if the synchronizing b/w
generator and busbar not
complete and we close the
out going circuit breaker
of generator then what
happen ?
Answer Posted / milinda4p
IF the synchronization does not complete and if you close a cct breaker a severe arcing may occur and generator will trip instantaneously. Because the Generator sides voltages and bus side voltages do not match. To match the volatges following has to satisfied.
1. voltage magnitude
2. phase angle difference - 0
3. phase sequence - same
So at this condition there might be present voltage or phase angles or phase position mismatches. Say for example there exists a voltage magntude mismatch of 1 kV and when you close the cct breaker contact points have that voltage across them and this will cause severe current through contact points of breaker
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how to introduce yourself
application s to shunt coil
how does the thyistor work in dc drive?
In both 600/1000 V cable and 450/750 V cable, we can supply 415 V. However for distribution, all utilities are using only 600/100 V instead of 450/750 V. What is the reason?
define the non synchoronism of synchoronous machine in general g or m??
what happens when dc generator coupled with cycle shaft.also explain what happens when its loaded
what is the difference between earth leakage and earth fault?
i am electrical and elctronics engg passed out in 2009 want to attend for reliance placements.plz send me apttitude ,technical and hr question answers to my mail plz. my mail id-kat.bindas@gmail.com
if sf6 gas low in gis what will happen
What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr
I completed iti in2004 I was worked in A grade contractor can I get c licence
Air circuit breaker safety
Why is the frequency not changed during transformation of electrical energy in a transformer?
TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.
what is a synchronizing lamp ?