Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

For a certain load i need 100kw load ,In that case what
rating mccb should i use?

Answer Posted / chintan patel

It can be different for DC , 1phase AC , 3 phase AC , systems,

Lets calculate for all ,

1 ) For DC ( you have not mentioned Voltage but considering 230 V )

100 kw means 100000 watt

formula for DC power p= vi

100000= 230xi

i=100000/230= 434 amp

we always use current rating of the mccb is 1.5 times of full load current so we can use 434x1.5= 652 amp.
( if system is not running on full load select 630 Amp MCCB, if its on full load select 800A )


2 ) For 1phase AC,

Power: P = V I cos phi ( cos phi is power factor is not known assume 0.8 )

100000 W = 230 x I x 0.8
I = 543 Amp

we always use current rating of the mccb is 1.5 times of
full load current.
mccb required 543 Amp X 1.5 = 815 Amp
select 800 Amp MCCB

3)

If load is 3 phase AC ,

Power P = sqrt(3) x V x I x cos phi

100000 w = 1.73 x 415 x I x 0.8
I = 174

we always use current rating of the mccb is 1.5 times of
full load current.
mccb required 174 Amp X 1.5 = 261 Amp

( if system is not running on full load select 250 Amp MCCB,
if its on full load select 315 A )

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?

2080


What are the advantages and disadvantages of short-pitched winding?

1099


what is the size of ht cable of 33kv ht line and transformers ratings are 1 Mva and 5mva.please send formula also.

1460


List the characteristics of filter?

1072


why single phase to grd test in HV cable?why not 2 phase at a time?

2289


what is 3rd Harmonics? how it is generated in alternator

9486


WHaT IS THE CONCEPT OF INDUCTION LAMPS IN MODERN LIGHTINGS, and HOW IT WORKS TO EMIT LIGHT ( AS NO ELECTRODES ARE PRESENT ) ?" COULD INDUCTION LAMPS CAUSE INTERFERENCE WITH COMUNICATIONS INTO A STORE USING INDUCTION LIGHTING ? WHAT IS THE BENEFIT OF USING THE LOW FREQENCY INDUCTION LAMP , VERSUS LED , AND VERSUS FLUORESCENT, AND VERSUS ANOTHER KIND OF LIGHTING . THANK yOU MOISES GUINDI

2069


Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028

1977


how we can adjust for three phase motor cold stall time ,hot stall time and thermal register set up?

2889


WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?

6360


what are the safety measures of induction motor?

2048


how 650 volts creates? where is use?

2214


what is mind in cable

2071


If we use 250A MCCB as a incomer in Control panel for a fault level of 50kA for one second ,assuming temperature rise from 85 Deg. to 100 Deg , Then what will be the Aluminium Bus-bar size for 250A MCCB? Explain in detail.

2345


Explain about technical and non technical losses in distribution system?

1069