We have yokogawa cs3000 one fcs and 4 his. After download to his, showing successfully at es, but not transferred to his.
Answer Posted / jigaranadkat
Dear,
First of all question is not clear that you are downloading what ? presume that you are downloading Graphics as other configuration will be downloaded to FCS and then automatically it will be "Equalized" to all HIS.
When you download any graphic in Engineering work station, the particular graphic will not appear in HIS unless you have pasted same graphics shortcut to any HIS. So, you can follow this procedure :
1) PASTE shortcut in respective HIS.
2) Once you download the required graphic in Engineering workstation the close the builder and select the particular graphic and in TOOLS MENU select the option DOWNLOAD TO HIS.
By this your graphic will be EQUALIZED in all HIS where you have pasted the shortcut of that graphic.
Fell free to post your result or any further question on :
Jigar Anadkat
E-mail : anadkat.jigar@gmail.com
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
hello can yoy pls send me previous papers of jindalpower and steel ltd.....'m from instrumentation..... mani1048@gmail.com
how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i
What is furnace draft control?
TECHNICAL/ARTITUDE
NSV type probe stands for
What inherent design and operating principles are included in a modern control system to use predictive maintenance practices to increase overall system reliability?
Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,
How to calibrate smoke Dectector
line up procedure for dp type flow transmitter?
Explain the difference between mmwc and mmwg?
what is span value and zero ? and how set ?
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
how do i tune dearator pr control valve using PID. we set the set point is 0.6kg/cm2 now i want 0.5 to 0.7kg/cm2 limits so what should i give p,i,d values. then pls explain how do set pid values for control valve tuning?
which processor is used in dcs.
Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram