We have yokogawa cs3000 one fcs and 4 his. After download to his, showing successfully at es, but not transferred to his.
Answer Posted / jigaranadkat
Dear,
First of all question is not clear that you are downloading what ? presume that you are downloading Graphics as other configuration will be downloaded to FCS and then automatically it will be "Equalized" to all HIS.
When you download any graphic in Engineering work station, the particular graphic will not appear in HIS unless you have pasted same graphics shortcut to any HIS. So, you can follow this procedure :
1) PASTE shortcut in respective HIS.
2) Once you download the required graphic in Engineering workstation the close the builder and select the particular graphic and in TOOLS MENU select the option DOWNLOAD TO HIS.
By this your graphic will be EQUALIZED in all HIS where you have pasted the shortcut of that graphic.
Fell free to post your result or any further question on :
Jigar Anadkat
E-mail : anadkat.jigar@gmail.com
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.
what is insdustrial vibration.who it works. give atleast 2 types of insdustrial vibration
what is interlock system and why we use of this?
Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?
What is the difference between uv and ir scanners? and what is the workig principle of both
How does work A temperature valve or fv control valve in process plz brief me
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
Why humidity limit is 30 to 55 % for raw material storage?
Speedtronic system .
How to work temperature gauge?
Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?
how u calibrate pneumatic n motorized c/v?
What is force balance principle?
What is the calibration procedure of Drum level transmitter if range is 0 to -400 mmh2o in lab?